Strength and Durability

Financial Benefits | Environmental Benefits | Health & Safety | Durability | Comfort & Quiet | FAQs

 

Structural Load Resistance: ICFs vs. Steel and Wood-Frame


Research was conducted to compare insulating concrete form (ICF) walls and conventionally framed walls, in terms of their ability to resist structural stresses that can occur during earthquakes. All of the walls were tested by applying a sideward or lateral force along the top edge of each wall, in line with the plane of the wall, while restraining the bottom. This "racking" of the specimens creates internal tearing or shear forces as the top of the wall tries to move while the bottom of the wall remains stationary. The concrete walls demonstrated significantly higher structural capacity and stiffness to resist the in-plane shear forces than wood or steel frame walls.

 

What types of walls were tested?


One wall specimen for each of five types of exterior residential wall systems were tested, each 8 feet high and 4 feet wide. Three of the wall specimens were built with ICFs, creating one flat concrete wall, a waffle grid concrete wall, and a screen grid concrete wall, all shown below. The walls were reinforced with grade 60 steel rebars. Additional steel extended from the top of the footing into each wall. The nominal compressive strength of the concrete used in the wall panels was 2500 psi. No finishes were applied to the surfaces of the wall specimens. Loads were applied to a concrete beam secured to the top of the wall panels with high-strength anchor bolts to transfer the lateral forces to the top of the specimens. The foam plastic formwork was removed from one side of each panel, in order to allow the concrete's performance to be observed.

 

icf test photo icf test photo icf test photo

 

 

The two frame walls consisted of a 2x4 wood stud specimen and a 20-gauge steel stud specimen. The framing was covered with 7/16-in. OSB (Oriented Strand Board) on one side and gypsum wallboard on the other. The frame walls were secured to concrete footings with steel hold-downs anchoring the ends, and with embedded anchor bolts at two intermediate locations. A 6-inch-deep timber beam was firmly attached to the top of the frame wall specimens to transfer the lateral forces to the top of the panels.


How was in-plane shear resistance measured?


The structural details for the test specimens were adopted based on design recommendations and guidelines for typical exterior wall panels in earthquake zones 1 or 2, and for minimum wind speed of up to 70 miles per hour. The test setup and procedure followed general guidelines of ASTM E564-95, Standard Practice for Static Load Test for Shear Resistance of Framed Walls for Buildings.
A hydraulic ram was used to transfer lateral load to the beam at the top of each wall. A calibrated instrument measured the increasing magnitude of this load. Additional devices were used to measure any movement of the panels or footing. The amount of load was gradually increased as any distress, cracking, or damage was observed and recorded. The loading was typically continued beyond the peak loading capacity of each wall, and testing terminated when the strength of each wall was significantly reduced due to excessive damage to the wall specimens.


How does the shear resistance compare?


The frame walls showed initial damage at relatively light loading, and had a much lower maximum lateral resistance. The ICF walls resisted a maximum lateral load of 6 to 8 times the maximum loads resisted by the frame wall panels. Under lateral loads of about twice as much as the maximum resistance of the frame walls, the ICF panels were still very stiff with extremely small deformation, and showed no damage. The table below summarizes the actual results for each tested wall panel.

 

In Plane Shear Wall Testing and Loading Results

Wall
Panel
Global Lateral Stiffness (lbs/in)* Load at First Major Damage (lbs) Displacement at First Major Damage (in) Maximum Lateral Resistance (lbs) Displacement at Maximum Lateral Resistance (in)
Wood Frame

18,500

3,500 0.51 4,553 0.89
Steel Frame

30,000

3,500 0.54 4,004 0.76
ICF Flat

708,000

8,500 0.06 34,245 2.66
ICF Waffle Grid

662,000

9,000 0.07 28,946 1.64
ICF Screen Grid

526,000

8,600 0.05 27,889 1.71

*Global Lateral Stiffness at 1/3 the maximum lateral force resistance for the wood and steel frame, at a lateral load of 5,000 lbs. for the ICF walls.

 

What does this difference mean?


These results suggest that when subjected to lateral in-plane loading from sources such as wind or earthquakes, the ICF wall panels are not only considerably stronger, but also much stiffer than the framed wall panels. The higher strength of ICF walls enable concrete buildings to resist winds and earthquakes of much higher magnitudes. The greater stiffness demonstrated by the ICF wall panels at the loading limits of the frame wall systems would result in smaller lateral deformation, as well as the prevention of potential damage to non-structural elements of a building such as finishes and trim. In the case of moderate earthquakes, the repair cost of the damaged non-structural components is usually the main portion of the restoration cost, and sometimes the only. ICFs offer great potential for reduced property loss from strong wind and earthquakes.


More Information?


The following publication is available from the Portland Cement Association:

In-Plane Lateral Load Resistance of Wall Panels in Residential Buildings, by Armin B. Mehrabi, Construction Technology Laboratories for Portland Cement Association, 2000, Serial No. 2403

 

This report documents the results of comparative in-plane shear wall testing conducted on wood/metal frame and ICF wall specimens. The panels represent some of the typical wall systems being used in current building construction. Full results of the testing is reported. The test setup and procedure followed the general guidelines of the ASTM E564-95, Standard Practice for Static Load Test for Shear Resistance of Framed Walls for Buildings.

To order, call PCA Publications at (800) 868-6733.